RPS Series – Linear UPS Power Supplies
Redundant Power Distribution with Battery Backup. Mid-Eastern Redundant Power System (RPS Series) units are employed in mission-critical Continuous Batch Processing applications requiring 24/7/365 uptime. All system components are isolatable and hot-swappable.
FEATURES SUMMARY:
- Metered AC Input Panel
- AC/DC Disconnect Panels
- Cooling System
- Status & Alarm Panel
- Individual Power Supplies
- DC Distribution Panels
- Battery Backup
- Battery Charger
- Description
- Data Sheets
Description
Mid-Eastern’s Redundant Power System (RPS Series) Linear UPS Power Supply features redundant Power Distribution with Battery Backup. These units are usually employed in mission-critical Continuous Batch Processing applications requiring 24/7/365 uptime. All system components are isolatable and hot-swappable.
FEATURES:
Metered AC Input Panel
AC source circuits are protected by a Main Breaker. A green indicator, volt and ammeters provide AC status. All subassemblies are protected and isolatable using individual AC and DC breakers.
AC/DC Disconnect Panels
Dedicated AC and DC circuit breakers protect the individual power supplies and provide for individual control/shutdown/replacement of any power supply without disrupting operation.
Cooling System
Each supply has separate fans, and rack blowers bring cool, filtered air in at bottom and exhaust heat out upper vents. The system is thermostatically controlled and monitored to sense any malfunctions.
Status & Alarm Panel
The RPS provides Audible, Visual and Remote Loop Alarms for any failure including Individual Supplies, Battery Backup & Charger Blowers or Distribution Breaker trips.
Individual Power Supplies
The RPS has 6 x (28 V @ 35 A) power supplies connected in a balanced parallel configuration using isolating diodes and DC breakers to provide a base capacity of 150 Amps DC (Expandable to 300 Amps).
DC Distribution Panels
The RPS incorporates 2 DC Distribution Panels with 2 rows of 15 x 10A (60 total) distribution breakers. The breakers feed Weidmuller DIN mount terminal blocks for connection of supplied loads.
Battery Backup
A UPS provides backup power in the event of AC power failure. The system will provide uninterrupted power at regulated 28 VDC at maximum current capacity of 150A for a full 30 minutes of run time.
Battery Charger
A separate charger keeps the UPS backup batteries at 100% readiness during normal operation. The system monitors power status and generates alarms if the UPS is active or faulting.