HV Series – SCR Pre-Regulated Linear Power Supplies
Constant Voltage/High Voltage Linear Power Supplies Up to 500V.
FEATURES:
- High Power – Small Size
- Remote Programmable
- Remote Sensing
- 0.01% Regulation
- ≤ 3 mV RMS Ripple
- 10 Turn Voltage Control
- 10 Turn Current Control
- Optional IEEE-488, LAN, RS485, RS232 Control
- Description
- Models
- Specifications
- Available Options
- Data Sheets
Description
The HV Series SCR Pre-Regulated Linear Power Supplies are high reliability sources providing high power, stable output regulation, very low noise, and very low output ripple. Their very low ripple and very low noise make them the preferred “Down Hole” power sources, as well as fixed and towed array systems power. The HV units have an adjustable current limiting circuit which provides output load protection. They are ideally suited for laboratory applications and in systems where both versatility of operation and a high degree of regulation are required.
The HV Series offers stable DC Power in 2U (3.5”) to 8U (14”) High 19” Full Rack Design for power ranging from 350W to 7000W (respectively) at 350 Volts.
3 ½” Models
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-1 | 0-350 V | 0-1 A |
5 ¼” Models
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-2 | 0-350 V | 0-2 A |
HV500-1 | 0-500 V | 0-1 A |
7″ Models
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-3 | 0-350 V | 0-3 A |
8 ¾” Models*
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-5 | 0-350 V | 0-5 A |
*8¾” Model: 220 VAC 50/60Hz 1Ø Standard
10 ½” Models**
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-10 | 0-350 V | 0-10 A |
12 ¼” Models**
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-15 | 0-350 V | 0-15 A |
14 ½” Models**
MODEL NUMBER | VOLTAGE | AMPS |
---|---|---|
HV350-20 | 0-350 V | 0-20 A |
**10½” Model and above: 230 VAC 50/60Hz 3Ø Standard
Input:
3½” to 7” : 115 VAC ± 10% 50/60 Hz 1Ø Standard
8¾” : 220 VAC ± 10% 50/60 Hz 1Ø Standard
10½” to 14” : 230 VAC ± 10% 50/60 Hz 3Ø Standard
Output: See specific model in table.
The output is floating and either side may be grounded.
Load Regulation: 0.01% of the maximum rated voltage for a full load step.
Line Regulation: 0.01% of the maximum rated voltage for a line change within specified input voltage range.
Ripple: ≤3 mV RMS.
Response Time: The output voltage is within regulation limits in less than 100 microseconds for a ½ load step. The output voltage will remain within regulation limits for input line step within specified voltage range.
Remote Sensing: Units provided with remote sense terminals at the rear for regulation at the point of load.
Remote Programming: All units are voltage programmable at approximately 1000Ω / Volt.
Series / Parallel Operation: Two or more units may be operated in series. Two units of the same voltage and current may be operated in parallel.
Temp. Coef.: 0.01% / °C
Stability: Better than 0.05% / 8 hours at constant line, load and temperature after ½ hour warm up.
Operating Temperature: 0°C to +60°C at any combination of line, load and temperature without the need for external cooling.
Terminations: AC line cord is provided for 3½” and 5¼” models. All other models have barrier terminal strip for AC input.Barrier terminal strips are provided at the rear for output, sensing, remote programming, slaving and ground.
Protection: The power supply is protected by a fuse in the input line. 8¾” models and above are protected by a circuit breaker. The power supply is protected by means of a fully adjustable current limiting circuit.
Panel Controls: Voltmeter, Ammeter, 10 turn voltage control, 10 turn current control, pilot light and ON/OFF switch. The voltage and current control is fully adjustable from 0 to Full Range by means of 10 turn panel potentiometers.
Finish: The standard front panel finish is light blue.
Size: 3½” to 7” : 19”(WIDE) x 16½” (DEEP)
All other models: 19”(WIDE) x 22” (DEEP)
OPTION | DESCRIPTION |
---|---|
6 | Over Voltage Protection |
27 | Chassis Slides |
29 | Optional 220 VAC Input |
36 | Voltage/Voltage Programming (0-10V = Full Rated Output Voltage) |
52 | Voltage/Current Programming (0-10V = Full Rated Output Current) |
62 | 3½ Digit Digital Meters |
85 | Voltage/Voltage Programming (Isolated Input 0-10V = Full Rated Voltage) |
90 | Voltage/Current Programming (Isolated Input 0-10V = Full Rated Current) |
108 | RS232 Control with Readback |
110 | RS485 Control with Readback |
112 | IEEE-488 Control with Readback |
123 | RJ45 Control with Readback |